OneLiner type-3 wind generator model issues
- ASPEN Support
- Jul 27, 2022
- 1 min read
A number of you have reported problems in simulating type-3 wind plants in OneLiner version 15 (up to and including v15.5):
Branch currents did not add up to zero at some buses.
Wind plants that were labeled "shut down" were still injecting current.
Upon further analysis, we discovered that problems happen when:
a) The fault was simulated with prefault-voltage profile of "From a linear network solution" And
b) The type-3 wind plant injects current in the network in pre-fault due to non zero MW unit generation or the initial terminal bus voltage being off-nominal.
The latest OneLiner maintenance release V15.6 has fixed all the above issues.
Users should contact ASPEN support to request the latest software update.