Issue in OneLiner V14 ANSI x/r results
- ASPEN Support
- May 18, 2016
- 1 min read
Updated: Jan 9, 2024
We discovered that OneLiner V14 produced incorrect ANSI x/r results in some networks when fault simulation options of "Iterative short circuit solution" of MOV protected series capacitor and/or "Enforce current limit" of current limited generators are enabled. These errors could potentially affect the Breaker Rating Module results as well.
This programming error had been fixed in OneLiner V14.3 with build number 30575 and higher (Program build number is display in OneLiner Help | About dialog box). Users should contact ASPEN support to request program update with this bug fix.
Yorumlar