top of page

POST

Issue in OneLiner Boundary Equivalent command

The Network | Boundary Equivalent command in OneLiner Version V14.5 and earlier had a bug that made the positive- and negative-sequence impedance of equivalent phase shifters too large by the factor of cosine(shift angle).


This problem has been fixed in OneLiner V14.6.


We had created a PowerScript program FixEquivBr.BAS that you can use to fix this problem in your OLR files.  This script file is in the .\Script directory of V14.6 program folder.  You can also download this script from ASPEN PowerScript exchange on GitHub:


Recent Posts

See All

Comments


©1986-2025 Advanced Systems for Power Engineering, Inc. All Rights Reserved.

bottom of page