This section contains parameters of converter-interfaced resource. The first line in the section must say: [CONVERTER-INTERFACED RESOURCE DATA]. This is followed by the data described below. A blank line ends the section. The terms “voltage” and “current” below refer to positive-sequence voltage and current unless specified otherwise.
1. Bus Name: Name of the bus to which the current source is attached, in quotation marks.
2. Base kV: Nominal kV of the current-source bus.
3. In-Service Flag: 1 if the current source is in service; 0 if it is not. The default value is 1.
4. Number of units: Number of type-4 wind generators or solar inverter units in this plant.
5. Unit MVA Rating
6. Unit rated MW.
7. Unit MW generation.
8. Reserved field: Enter a constant 0..
9. Maximum current output when voltage is higher than the threshold as a multiple of the full load current
10. Maximum current output transition voltage threshold
11. Maximum current output when voltage is lower than the threshold as a multiple of the full load current
12. Low voltage generator shutdown threshold in per-unit
13. High voltage generator shutdown threshold in per-unit
14. Reserved field: Enter a constant 0
15. Slope of the positive-sequence reactive injection characteristics
16. Slope of the negative-sequence reactive injection characteristics
17. Reserved field: Enter a constant 0
18. In-service Date: Set to 0 if not available. Otherwise enter an unsigned 32-bit integer that store the year/month/date information given by the CTime object in Microsoft Foundation Class.
19. Out-of-Service Date: Set to 0 if not available. Otherwise enter an unsigned 32-bit integer that store the year/month/date information given by the CTime object in Microsoft Foundation Class.
20. Reserved field: Enter a constant 0
21. Reserved field: Enter a constant 0
22. Reserved field: Enter a constant 0
23. Reserved field: Enter a constant 0
24. Memo: Comments with a maximum of 512 characters. Any alpha-numeric characters can be used, except for the string delimiter (single or double quotation mark). The comment text is enclosed in quotation marks.
25. Tags: Tag string with a maximum of 512 characters. Tags in string are separated by semicolon. Any alpha-numeric characters can be used, except for the string delimiter (single or double quotation mark). The tag string is enclosed in quotation marks.
26. UDF: User-defined data fields. Enter the list of user defined field values as a tab delimited text string enclosed in single quotes.
An example voltage controlled current source data section is shown below.
[CONVERTER-INTERFACED RESOURCE DATA]
'MARYLAND' 33 = 1 10 10 0 0 1.1 0.5 1.1 /
0.05 1.2 0 2 0 0 0 0 0 0 0 0 0