This section contains parameters of type-3 wind plants. The first line in the section must say: [TYPE-3 WIND PLANT DATA]. This is followed by the data described below. A blank line ends the section. The terms “voltage” and “current” below refer to positive-sequence voltage and current unless specified otherwise.
1. Bus Name: Name of the bus to which the current source is attached, in quotation marks.
2. Base kV: Nominal kV of the current-source bus.
3. In-Service Flag: 1 if the current source is in service; 0 if it is not. The default value is 1.
4. Number of units: Number of type-3 wind generators (units) in this plant.
5. Unit MVA Rating
6. Unit rated MW.
7. Unit MW generation.
8. Crowbarred flag: Enter 1 for true; 0 for false.
9. Low voltage generator shutdown threshold in per-unit
10. High voltage generator shutdown threshold in per-unit
11. Reserved field: Enter a constant 0
12. Reserved field: Enter a constant 2
13. Converter current limit on rotor side in per-unit.
14. Converter current limit on grid side in per-unit.
15. Stator resisstance
16. Stator leakage inductance
17. Rotor resistance
18. Rotor leakage inductance
19. Mutual inducance
20. Slip rate at rated kW
21. Filter reactance at power frequency
22. In-service Date: Set to 0 if not available. Otherwise enter an unsigned 32-bit integer that store the year/month/date information given by the CTime object in Microsoft Foundation Class.
23. Out-of-Service Date: Set to 0 if not available. Otherwise enter an unsigned 32-bit integer that store the year/month/date information given by the CTime object in Microsoft Foundation Class.
24. Memo: Comments with a maximum of 512 characters. Any alpha-numeric characters can be used, except for the string delimiter (single or double quotation mark). The comment text is enclosed in quotation marks.
25. Tags: Tag string with a maximum of 512 characters. Tags in string are separated by semicolon. Any alpha-numeric characters can be used, except for the string delimiter (single or double quotation mark). The tag string is enclosed in quotation marks.
26. UDF: User-defined data fields. Enter the list of user defined field values as a tab delimited text string enclosed in single quotes.
An example voltage controlled current source data section is shown below.
[TYPE-3 WIND PLANT DATA]
'OHIO' 132 = 1 10 10 1 1 0 0.05 1.2 /
0 2 1.1 0.35 0.03 0.2 0.03 0.2 3 -0.2 -20 0 0