9.10  TYPE-3 WIND PLANT DATA

This section contains parameters of type-3 wind plants. The first line in the section must say:  [TYPE-3 WIND PLANT DATA].  This is followed by the data described below.  A blank line ends the section.  The terms “voltage” and “current” below refer to positive-sequence voltage and current unless specified otherwise.

1.   Bus Name: Name of the bus to which the current source is attached, in quotation marks. 

2.   Base kV: Nominal kV of the current-source bus.

3.   In-Service Flag: 1 if the current source is in service; 0 if it is not.  The default value is 1.

4.  Number of units: Number of type-3 wind generators (units) in this plant.

5.  Unit MVA Rating

6.   Unit rated MW.

7.  Unit MW generation.

8.  Crowbarred flag: Enter 1 for true; 0 for false.

9.   Low voltage generator shutdown threshold in per-unit

10. High voltage generator shutdown threshold in per-unit

11. Reserved field: Enter a constant 0

12. Reserved field: Enter a constant 2

13. Converter current limit on rotor side in per-unit.

14. Converter current limit on grid side in per-unit.

15. Stator resisstance

16. Stator leakage inductance

17. Rotor resistance

18. Rotor leakage inductance

19. Mutual inducance

20. Slip rate at rated kW

21. Filter reactance at power frequency

22. In-service Date: Set to 0 if not available. Otherwise enter an unsigned 32-bit integer that store the year/month/date information given by the CTime object in Microsoft Foundation Class.

23. Out-of-Service Date: Set to 0 if not available. Otherwise enter an unsigned 32-bit integer that store the year/month/date information given by the CTime object in Microsoft Foundation Class.

24. Memo: Comments with a maximum of 512 characters.  Any alpha-numeric characters can be used, except for the string delimiter (single or double quotation mark).  The comment text is enclosed in quotation marks.

25. Tags: Tag string with a maximum of 512 characters.  Tags in string are separated by semicolon. Any alpha-numeric characters can be used, except for the string delimiter (single or double quotation mark).  The tag string is enclosed in quotation marks.

26. UDF: User-defined data fields. Enter the list of user defined field values as a tab delimited text string enclosed in single quotes.

An example voltage controlled current source data section is shown below.

[TYPE-3 WIND PLANT DATA]

'OHIO' 132 = 1 10 10 1 1 0 0.05 1.2 /

 0 2 1.1 0.35 0.03 0.2 0.03 0.2 3 -0.2 -20 0 0