10.13 RELAY GROUP

The record for a relay group is shown below.  The first line must have the words RELAYGROUP, starting at column 1.  The remaining data starts on the next line and can occupy one or more lines.  The record ends with a blank line.

RELAYGROUP

BUS_NO1;  BUS1;  KV1;  BUS_NO2;  BUS2;  KV2;  CKT;  BTYP;

MEMO;

TAG;

BKRINTRPTIME;RECLOSEINT1;RECLOSEINT1;RECLOSEINT1;

TRIPLOGIC;RECLOSELOGIC;

MEMO:  Relay group comments with up to 512 characters enclosed in quotation marks.

TAG: Tag string with a maximum of 512 characters.  Tags in string are separated by semicolon. Any alpha-numeric characters can be used, except for the string delimiter (single or double quotation mark).  The tag string is enclosed in quotation marks.

BKRINTRPTIME: Breaker interrupting time in cycles.

RECLOSEINT1: First reclosing interval in seconds. This field must be zero if the breaker is set for single operation (no reclosing). The reclosing intervals are for relay groups on lines and switches only.

RECLOSEINT2: Second reclosing interval in seconds. This field must be zero if the breaker is set for less than two operations.

RECLOSEINT3: Third reclosing interval in seconds. This field must be zero if the breaker is set for less than three operations.

TRIPLOGIC: Trip logic scheme name enclosed in quotations marks. Use empty string to indicate trip by fastest device in the group.

RECLOSELOGIC: Reclose logic scheme name enclosed in quotations marks. Use empty string to indicate “Always” reclose logic.